What is Fire-Rated Glass and Framing?


What is the difference between fire-protective and fire-resistive glazing?

When specifying fire-rated glazing, it is crucial to understand the difference between fire-protective vs. fire-resistive glazing products (technically referred to as fire-protection rated and fire-resistance rated):

Fire protective: Fire protective means the glazing defends against the spread of flames and smoke for its designated fire rating. Such materials include traditional wired glass, glass ceramics, and specially tempered glass. Fire-protective glazing typically is suitable where building codes allow “opening-protective” assemblies, including doors, sidelites, and windows. Such glazing is available with fire ratings ranging from 20 to 180 minutes, with varying impact safety ratings. Since it does not block the transfer of radiant and conductive heat, it is subject to area and size limitations under the applicable building code (typically the International Building Code – IBC, in the U.S.) and/or authority having jurisdiction.

Fire resistive: Fire resistive glass provides the same defense against flames and smoke as fire-protective glazing, but adds further protection by blocking the transfer of radiant and conductive heat. It is tested to the stringent fire-resistance test standards for walls, including ASTM E119: Standard Test Methods for Fire Tests of Building Construction and Materials and Underwriters Laboratories (UL) 263: Fire-resistance Ratings.

Given these performance benefits, fire-resistive glazing assemblies are typically suitable where building codes require an assembly designated “fire resistant” to enclose a space. Examples include wall applications requiring a 60-minute or greater fire rating that must meet temperature-rise criteria, such as stairwells, exit access corridors, or other fire barriers dividing interior construction. Due to its heat-blocking characteristics and classification as fire-resistive wall construction, it is not restricted to 25 percent of the wall area. This provides design teams with greater flexibility when working to create light-filled and inviting spaces that meet strict fire and life safety criteria.

Sign up for TGP's Newsletter

Send me emails about product info, continuing education opportunities and other news from Technical Glass Products

Click here to dismiss this window.

By clicking submit, you agree to this web site’s terms of use. To unsubscribe from receiving emails from Technical Glass Products, click the Unsubscribe link at the bottom of our emails or contact Allegion at dataprivacy@allegion.com. You understand and agree that your information may be transferred into the United States or other locations outside your country of residence. For more information on our privacy practices, please see our Privacy Policy.